380V 60KVA outdoor UPS.png

IP65 3 Phases Outdoor Rugged waterproof 10-100KVA industrial UPS

Custom 3-Phase IP65 Outdoor Industrial UPS Uninterruptible Power Supply Key Features: True IP65 Waterproof & Dustproof – No external cabinet needed; direct outdoor installation in rain, snow, dust, or high-humidity areas. 3-Phase Industrial Topology – 380V/400V/415V I/O, compatible with global industrial equipment. Wide Temperature Range – -25℃ to +55℃ (optional -40℃), with integrated heater + fan thermal management. Fully Customizable – Battery type (LiFePO₄/AGM), enclosure material (stainless steel / painted steel), communication ports (Modbus/SNMP/ dry contact), and I/O terminals. Outdoor-Ready Design – UV-resistant coating, pole or ground mounting, bottom cable entry. Typical Use Cases: Intelligent traffic (traffic lights, radar, ETC) Oil & gas remote sites Outdoor 4G/5G telecom base stations Ports & offshore platforms Solar + storage integration Why Cooperate: 10+ years in industrial power protection OEM/ODM with flexible MOQ CE, IEC, TUV, IP65 test reports available

Category:

Downloads:

  • Overview
  • Specifications
  • Download
    • Commodity name: IP65 3 Phases Outdoor Rugged waterproof 10-100KVA industrial UPS
    • Commodity ID: IP65 UPS 10-100KVA

    Custom 3-Phase IP65 Outdoor Industrial UPS Uninterruptible Power Supply Key Features: True IP65 Waterproof & Dustproof – No external cabinet needed; direct outdoor installation in rain, snow, dust, or high-humidity areas. 3-Phase Industrial Topology – 380V/400V/415V I/O, compatible with global industrial equipment. Wide Temperature Range – -25℃ to +55℃ (optional -40℃), with integrated heater + fan thermal management. Fully Customizable – Battery type (LiFePO₄/AGM), enclosure material (stainless steel / painted steel), communication ports (Modbus/SNMP/ dry contact), and I/O terminals. Outdoor-Ready Design – UV-resistant coating, pole or ground mounting, bottom cable entry. Typical Use Cases: Intelligent traffic (traffic lights, radar, ETC) Oil & gas remote sites Outdoor 4G/5G telecom base stations Ports & offshore platforms Solar + storage integration Why Cooperate: 10+ years in industrial power protection OEM/ODM with flexible MOQ CE, IEC, TUV, IP65 test reports available

     OEM ODM Custom 3-Phase IP65 Outdoor Industrial UPS Uninterruptible Power Supply

    Key Features:

    True IP65 Waterproof & Dustproof – No external cabinet needed; direct outdoor installation in rain, snow, dust, or high-humidity areas.

    3-Phase Industrial Topology – 380V/400V/415V I/O, compatible with global industrial equipment.

    Wide Temperature Range – -25℃ to +55℃ (optional -40℃), with integrated heater + fan thermal management.

    Fully Customizable – Battery type (LiFePO₄/AGM), enclosure material (stainless steel / painted steel), communication ports (Modbus/SNMP/ dry contact), and I/O terminals.

    Outdoor-Ready Design – UV-resistant coating, pole or ground mounting, bottom cable entry.

    Typical Use Cases:

    Intelligent traffic (traffic lights, radar, ETC)

    Oil & gas remote sites

    Outdoor 4G/5G telecom base stations

    Ports & offshore platforms

    Solar + storage integration

    Why Cooperate:

    10+ years in industrial power protection

    OEM/ODM with flexible MOQ

    CE, IEC, TUV, IP65 test reports available

  • Model10KVA
     
    15KVA20KVA30KVA40KVA60KVA80KVA100KVA
    Capacity10KVA
     
    15KVA20KVA30KVA40KVA60KVA80KVA100KVA
    System parameters
    Relationship between output power factor cosφ and the load 
    0.5~0.8 inductive load100%
    0.8~1.0 inductive load100~80%
    1.0 linear Load80%
    0.8~1.0 capacitive load80%
    0.5~0.8 capacitive load70%
    Computer load80%
    Overall efficiency (normal mode) Load 100%92%
    50% load90%
    Overall efficiency (economic model):100% load
    98%
    Max. leakage current(mA)100
    Standby economy modeStandard function
    Mean time between failure(MTBF)200,000hours
    Computer monitoring interfaceStandard configuration RS232, RS485 / MODBUS
    Operating temperature0 ~ 40 °C
    Max relative humidity95 % (non-condensing)
    CoolingForced ventilation (fan speed varies with load and temperature)
    Maximum altitudeRated power at 1000m (Reduce by -1% for every 100 meters rise), maximum 4000m
    Noise dB52 ~62
    Protection class(EN 60529)IP20
    Incoming and outgoing line methodIncoming from bottom
    Safety standardSafety regulations:GB4943, EN 50091-1; EMC: GB7260.2,GB/T 17626.2~5EMC, EN 50091-2
    Physical parameters
    Width (mm)540550For reference only
    Depth * Height (mm)  657*1132725*1290
    Weight (Kg)170
    250
    295
    335
    190200210260380430
    Rectifier input
    Rated voltage380/400/415VAC  Three phase three wire
    Voltage range± 15 %  (± 25 % adjustable)
    Rated frequency50 / 60 Hz   (        Automatic identification)
    Rated frequency45 ~ 65
    Input power pre-charge functionYes, 0-100%, can be set in 10-300 seconds
    Input power factor  cosφ:Up to 0.99 (with harmonic filter)
    Input current harmonic component(THD)Minimum<5% (with harmonic filter)
    Max. input current [A]1827365572108130 

     

    Model10KVA
     
    15KVA20KVA30KVA40KVA60KVA80KVA100KVA
    Capacity10KVA
     
    15KVA20KVA30KVA40KVA60KVA80KVA100KVA
    System parameters
    Relationship between output power factor cosφ and the load 
    0.5~0.8 inductive load100%
    0.8~1.0 inductive load100~80%
    1.0 linear Load80%
    0.8~1.0 capacitive load80%
    0.5~0.8 capacitive load70%
    Computer load80%
    Overall efficiency (normal mode) Load 100%92%
    50% load90%
    Overall efficiency (economic model):100% load
    98%
    Max. leakage current(mA)100
    Standby economy modeStandard function
    Mean time between failure(MTBF)200,000hours
    Computer monitoring interfaceStandard configuration RS232, RS485 / MODBUS
    Operating temperature0 ~ 40 °C
    Max relative humidity95 % (non-condensing)
    CoolingForced ventilation (fan speed varies with load and temperature)
    Maximum altitudeRated power at 1000m (Reduce by -1% for every 100 meters rise), maximum 4000m
    Noise dB52 ~62
    Protection class(EN 60529)IP20
    Incoming and outgoing line methodIncoming from bottom
    Safety standardSafety regulations:GB4943, EN 50091-1; EMC: GB7260.2,GB/T 17626.2~5EMC, EN 50091-2
    Physical parameters
    Width (mm)540550For reference only
    Depth * Height (mm)  657*1132725*1290
    Weight (Kg)170
    250
    295
    335
    190200210260380430
    Rectifier input
    Rated voltage380/400/415VAC  Three phase three wire
    Voltage range± 15 %  (± 25 % adjustable)
    Rated frequency50 / 60 Hz   (        Automatic identification)
    Rated frequency45 ~ 65
    Input power pre-charge functionYes, 0-100%, can be set in 10-300 seconds
    Input power factor  cosφ:Up to 0.99 (with harmonic filter)
    Input current harmonic component(THD)Minimum<5% (with harmonic filter)
    Max. input current [A]1827365572108130 

     

    Rectifier output


    Maintenance voltage (20°C)
    Battery type 1 and 2:V = (2.266 * el.) Vdc
    Battery type 3:V = (2.21 * el.) Vdc
    Battery type 0:The voltage value is between type 1 and 2, and the voltage value adjustment range V =(2.09~2.4) * el. [Vdc]


    Charging Voltage (20°C)
    Battery type 1 and 2:V(% Recharging<95%)= (2.32 * el.) Vdc
    Battery type 3:V(% Recharging<95%)= (2.4 * el.) Vdc
    Battery type 0:The voltage value is between type 1 and 2, and the voltage value adjustment range V =(2.09~2.4) * el. [Vdc]
    Max. charging voltage(2.32 * el.) Vdc
    Charger output voltage stabilization accuracy1%
    DC ripple voltage component≤1%
    Battery
    Number of units (rated voltage)174 units(348VDC)~240 units(480VDC)
    Charging current setting0.1A x C10



    Battery discharge termination voltage
    Battery  1, 2 and  3:No-load discharge current, Vmin=(1.81 * el.)   [Vdc]
    Battery  1, 2 and 3:output current=Ah Capacity, Vmin=(1.65 * el.)  [Vdc]
    Battery 1, 2 and 3:output current>Ah Capacity, Vmin=(1.60 * el.)  [Vdc]
    Battery 0 type: Factory default values, Vmin=(1.67 * el.)   [Vdc] Adjustment range Vmin =(1.57~1.88) * el. [Vdc]
    Single-phase inverter output
    Rated capacity [KVA]10203040506080 
    Rated power [KW]8162432404864 
    Rated voltage [V]220/230VAC
    Rated current [A]2972109145182218290 
    Phase voltage setting200 ~ 244 V (control panel)
    Peak factor(peak/Irms)3:1
    Wave formSine wave
    Voltage phase shift (degrees)
    100% balanced load

    ± 1'
    Voltage phase shift (degrees)
    100% unbalanced load

    ± 2'
    Phase voltage difference
    100% balanced load

    ± 1 %
    Phase voltage difference
    100% unbalanced load

    ± 3 %
    Total harmonic distortion(THDv)
    100% linear Load

    <2%
    Total harmonic distortion(THDv)
    100% non-linear Load

    <5%
    Steady voltage stability± 1 %
    Transient voltage response± 5 % within   10ms 
    Rated frequencySame as input
    Frequency stability± 0.5% when asynchronous; During synchronization, ± 2% (can be set to ± 1-5%, operated by the panel)
    Overload600' / 10' / 1' (110/125/150% Rated current)
    Short circuit for 0.1 seconds2 times input
    Rectifier output


    Maintenance voltage (20°C)
    Battery type 1 and 2:V = (2.266 * el.) Vdc
    Battery type 3:V = (2.21 * el.) Vdc
    Battery type 0:The voltage value is between type 1 and 2, and the voltage value adjustment range V =(2.09~2.4) * el. [Vdc]


    Charging Voltage (20°C)
    Battery type 1 and 2:V(% Recharging<95%)= (2.32 * el.) Vdc
    Battery type 3:V(% Recharging<95%)= (2.4 * el.) Vdc
    Battery type 0:The voltage value is between type 1 and 2, and the voltage value adjustment range V =(2.09~2.4) * el. [Vdc]
    Max. charging voltage(2.32 * el.) Vdc
    Charger output voltage stabilization accuracy1%
    DC ripple voltage component≤1%
    Battery
    Number of units (rated voltage)174 units(348VDC)~240 units(480VDC)
    Charging current setting0.1A x C10



    Battery discharge termination voltage
    Battery  1, 2 and  3:No-load discharge current, Vmin=(1.81 * el.)   [Vdc]
    Battery  1, 2 and 3:output current=Ah Capacity, Vmin=(1.65 * el.)  [Vdc]
    Battery 1, 2 and 3:output current>Ah Capacity, Vmin=(1.60 * el.)  [Vdc]
    Battery 0 type: Factory default values, Vmin=(1.67 * el.)   [Vdc] Adjustment range Vmin =(1.57~1.88) * el. [Vdc]
    Single-phase inverter output
    Rated capacity [KVA]10203040506080 
    Rated power [KW]8162432404864 
    Rated voltage [V]220/230VAC
    Rated current [A]2972109145182218290 
    Phase voltage setting200 ~ 244 V (control panel)
    Peak factor(peak/Irms)3:1
    Wave formSine wave
    Voltage phase shift (degrees)
    100% balanced load

    ± 1'
    Voltage phase shift (degrees)
    100% unbalanced load

    ± 2'
    Phase voltage difference
    100% balanced load

    ± 1 %
    Phase voltage difference
    100% unbalanced load

    ± 3 %
    Total harmonic distortion(THDv)
    100% linear Load

    <2%
    Total harmonic distortion(THDv)
    100% non-linear Load

    <5%
    Steady voltage stability± 1 %
    Transient voltage response± 5 % within   10ms 
    Rated frequencySame as input
    Frequency stability± 0.5% when asynchronous; During synchronization, ± 2% (can be set to ± 1-5%, operated by the panel)
    Overload600' / 10' / 1' (110/125/150% Rated current)
    Short circuit for 0.1 seconds2 times input

Message

SUBMIT
%{tishi_zhanwei}%