新ab6c013c-a6b8-4620-a822-aeed84eec6ff.jpg
新49f4a2ed-910f-4842-99e5-8515d3d49b4b.jpg
新39687321-5dad-4178-b109-2b34eea51089.jpg

CX1KVA-3KVA Online UPS High Frequency UPS

CX1-3K series high frequency online UPS is specially designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.

Downloads:

  • Overview
  • Specifications
  • Download
    • Commodity name: CX1KVA-3KVA Online UPS High Frequency UPS
    • Commodity ID: 1037782447900418048

    CX1-3K series high frequency online UPS is specially designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.

    CX1K-3K High Frequency Online UPS

    Application:

    CX1-3K series high frequency online UPS is specially designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.

     

    Features:

    * Advanced DSP numerical control technology application, the performance of UPS is more stable, more superior quality.

    * The load power factor is 0.8

    * Adopting digital control of active power factor correction technology, make the input power factor above 0.98, to avoid the pollution to power network, achieve energy saving, reduce the investment cost of the system.

    * A very wide range of input voltage and frequency, even in remote parts of electric power environment is very bad to normal power supply, reduce the number of battery discharge, improve the service life of the battery.

    * Can match generator to use, Input voltage and frequency range is wide, can effectively isolate the generator of electricity, to provide clean, safe and stable power supply load.

    * Grid is not stable, UPS power supply mode conversion time is zero, effectively ensure the security and reliability of the load operation.

    * Smart slot can provide abundant extensible function; can choose to install Win power, SNMP card.

     

  • Model

    CX1K

    CX1KL

    CX2K

    CX2KL

    CX3K

    CX3KL

    Capacity

    VA/W

    1000VA/800W

    1000VA/800W

    2000VA/1600W

    2000VA/1600W

    3000VA/2400W

    3000VA/2400W

    Input

    Nominal Voltage

    200/208/220/230/240VAC

    Voltage Range

    115~300VAC

    Harmonic Distortion

    <10% (Nonlinear load)

    Power Factor

    0.98

    Frequency Range

    50Hz:46~54Hz; 60Hz:56~64Hz

    Output

    Voltage

    200/208/220/230/240(1±1%)VAC

    Frequency

    50/60Hz (Adjustable); 
    50Hz AC Mode: Follow AC Mode (AC Range 46~54Hz); Battery Mode: 50Hz (1±0.2%)
    60Hz AC Mode: Follow AC Mode (AC Range 56~64Hz); Battery Mode: 60Hz (1±0.2%)

    Wave Form

    Pure sine wave

    Power Factor

    0.8

    Harmonic Distortion

    ≤4% (Linear load); ≤7% (Nonlinear load)

    Overload Capacity

    105%~150%  45S~25S; 150%~200%  25s~300ms; ≥200%  200ms

    Current Crest Ratio

    3∶1

    Connections

    IEC320*4

    Efficiency

    Battery Mode

    81%

    83%

    AC Mode

    85%

    87%

    Battery

    Type

    Sealed free maintenance lead acid battery

    Nominal DC voltage

    24VDC

    36VDC

    48VDC

    72VDC

    72VDC

    96VDC

    Quantity

    12VDC×2

    12VDC×3

    12VDC×4

    12VDC×6

    12VDC×6

    12VDC×8

    Backup Time (Full Load)

    ﹥2.5min

    (Built in batteries12V9AH)

    Depends on requested

    Back-up time

    ﹥5min

    (Built in batteries12V 9AH)

    Depends on requested

    Back-up time

    ﹥4.5min

    (Built inbatteries12V7AH)

    Depends on requested

    Back-up time

    Charge Current (Max)

    1A

    5A

    1A

    5A

    1A

    5A

    Charge Voltage (VDC)

    27.4V±0.2VDC

    41.1V±0.2VDC

    54.8V±0.4VDC

    82.2V±0.6VDC

    82.2V±0.6VDC

    110±0.6VDC

    Recharge Time

    7 hours filling to 90%

    (standard)

    Depends on external

    battery capacity

    (long-term)

    5 hours filling to 90%

    (standard)

    Depends on external 

    battery capacity

    (long-term)

    5 hours filling to 90%

    (standard)

    Depends on external 

     battery capacity

    (long-term)

    Bypass

    Automatic Transfer

    On overload and UPS failure

    Before UPS Power-on

    Default ”ON” user adjustable to “YES”

    Transfer Time

     

    0 ms; Less than 4ms from inverter to bypass and vice versa

    indicators

    LCD Display

    UPS status, Battery capacity, loading, Fault code
    (LCD: I/P &O/P voltage&frequency, Battery voltage)

    Audible

     

    Bypass, On battery mode, Battery low, Overload, Fault

    Acoustic Noise

    At 1 Meter Distance

    <45dB

    <50dB

    Communications

    Intelligent RS232

    serial port

    Software support Windows family software, Linux, Sun network operating system,        
    IBM Aix, Compaq True64 SGI IRIX, FreeBSD, HP-UX and MAC

    SNMP (Optional)

    Remote control UPS through SNMP management and Internet

    USB (Optional)

    Windows family software and Mac OS

    Environmental

    Operating

    Temperature

    0~40℃

    Operating

    Humidity

    20~90% (No condensing)

    Physical Parameter

    L*W*H (mm)

    373*145*219

    448*192*341

    Net Weight (Kgs)

    9.5

    5

    17.5

    9.5

    22

    10